Hot search:
 

CMS Modular UPS-100/10

Click on the image to check the artwork
unit price: negotiable
min amount:
amount:
period for delivery: Consignment Deadline Days
area: Beijing
Expiry date : Long Effective
last update: 2017-06-30 20:50
view count: 250
enquiry
Company Profile
 
 
Product details
Power range: 10KVA-100KVA 
Tech: high frequency modular UPS
Spec: 220/380VAC, 50/60Hz, 3-phase
App: medium and big datacenter 
System model:            CMS-100/10
System Max.Power:    100KVA
Module Model:             CM10III
Module Power:            10KVA
Configuration:              10 modules
System Dimensions:  600*800*1600 (W*D*H)mm    
Module Dimensions: 482*465*89 (W*D*H)mm
Components:            STS module, Monitor module,UPS module, Power distribution
Top or bottom feed
Description
Overview:
CMS UPS units are non-isolated, industrial level, green UPS, adopting advanced modular power protection concept. CMS Modular architecture can scale power as demand grows or as higher levels of availability are required. CMS UPS is industry-leading efficiency, availability, and performance for small, medium, and large data centers and mission critical environments.
Product Feature
Feature:
Rational redundant structure
UPS module: 10 kVA, 25 kVA, 50 kVA; System: 50kVA, 100 kVA, 150kVA, 250 kVA, 350 kVA, 500 kVA, 800 kVA.
Great performance index
overall efficiency > 95%(AC-AC), inverter efficiency > 98%(DC-AC), THDI < 3%, and input PF > 0.99
N+X module-level redundancy UPS System
Multi-level decentralized control technology and Master-slave synchronization in sequency control which result in eliminate system failure bottleneck
Each module automatically even shares the input and output current, all UPS modules share batteries
Battery management:
Battery discharge management, auto-transfer between floating and even charging, temperature compensation
Space-saving high density design, Rack-based for agility and aesthetics
Monitor Function
C/S-Oriented Architecture SICON Software which is available to monitor multiple UPS up to 600 sets;
B/S-Oriented Architecture which is available to check via IE
Standard configuration
Manual maintenance bypass, SPD(Class C), RS232, RS485/RS422 Communication ports, Remote monitor software, day contacts
Optional configuration
EPO, Input/output Transformer, Battery Bank, IPDS(Intelligent Power Distribution System)
Application:
IDC date center, government, telecom, bank, security, transportation, broadcast&TV network, HealthCare, Communication, E-business, Finance, etc.